Operation – KROHNE MFC 400 EN User Manual
Page 87

OPERATION
6
87
MFC 400
www.krohne.com
08/2013 - 4002075802 - MA MFC 400 R02 en
6.4.4 Set free units
C6.8 HART
C6.8
HART
C6.8.1
HART
Switch HART
®
communication on/off:
Select:
On (HART
®
activated) possible current range for current output 4…20 mA /
Off (HART
®
not activated) possible current range for current output
0…20 mA
C6.8.2
Address
Set address for HART
®
operation:
Select:
00 (Point-to-Point operation,;current output has normal function;
current = 4…20 mA) / 01...15 (Multi-Drop operation; current output has a
constant setting of 4 mA)
C6.8.3
Message
Set required text:
A…Z ; a…z ; 0…9 ; / - + , . *
C6.8.4
Description
Set required text:
A…Z ; a…z ; 0…9 ; / - + , . *
C6.8.5
HART Long tag
Set the HART Long tags
C6.9 Quick Setup
C6.9
Quick Setup
Activate quick access in the menu "Quick Setup"
Select: Yes (activated) / No (switched off)
C6.9.1
Reset Totaliser 1
Reset Totaliser 1 in menu "Quick Setup"
Select: Yes (activated) / No (switched off)
C6.9.2
Reset Totaliser 2
Reset Totaliser 2 in menu "Quick Setup"
Select: Yes (activated) / No (switched off)
C6.9.3
Reset Totaliser 3
Reset Totaliser 3 in menu "Quick Setup"
Select: Yes (activated) / No (switched off)
C6.9.4
Reset All Totalisers
Reset all Totaliser in menu "Quick Setup"
Select: Yes (activated) / No (switched off)
Free units
Sequences to set texts and factors
Texts
Texts
Texts
Texts
Volume flow, mass flow and density:
3 digits before and after the slash
xxx/xxx (max. 6 characters plus a "/")
Permissible characters:
A…Z; a…z; 0…9; / - + , . *; @ $ % ~ () [] _
Conversion factors
Conversion factors
Conversion factors
Conversion factors
Desired unit
= [unit see above] * conversion factor
Conversion factor
Max. 9 digits
Shift decimal point:
↑ to the left and ↓ to the right
.book Page 87 Monday, August 26, 2013 9:05 AM