4

ELECTRICAL CONNECTIONS

50

MFC 400

www.krohne.com

08/2013 - 4002075802 - MA MFC 400 R02 en

Control input active C

N

NAMUR, modular I/Os

• Connection acc. to EN 60947-5-6
• Switching point for identifying "contact open or closed":

Contact open (off): U

0, nom

= 6.3 V with I

nom

< 1.9 mA

Contact closed (on): U

0, nom

= 6.3 V with I

nom

> 1.9 mA

• Detection of cable break:

U

0

≥ 8.1 V with I ≤ 0.1 mA

• Detection of cable short circuit:

U

0

≤ 1.2 V with I ≥ 6.7 mA

• X designates the connection terminals A or B, depending on the version of the signal

converter.

CAUTION!
Observe connection polarity.

Figure 4-21: Control input active C

N

to NAMUR EN 60947-5-6