DESCRIPTION OF HART INTERFACE

9

139

MFC 400

www.krohne.com

08/2013 - 4002075802 - MA MFC 400 R02 en

9.4 Inputs/outputs and HART

®

dynamic variables and device variables

The signal converter is available with various input/output combinations.

The connection of the terminals A…D to the HART

®

dynamic variables PV, SV, TV and 4V depends

on the device version.

PV = Primary Variable; SV = Secondary Variable; TV = Tertiary Variable; 4V = Fourth Variable

The signal converter can provide up to 14 measurement-related values. The measured values
are accessible as so-called HART

®

device variables and can be connected to the HART

®

dynamic

variables. The availability of these variables depends on the device versions and the settings.

Code = device variable code

Device variables

Signal converter version

HART

®

dynamic variable

PV

SV

TV

4V

Basic I/O, connection terminals

A

D

-

-

Modular I/O and Ex i I/O, connection terminals

C

D

A

B

HART

®

device variable

Code

Type

Explanations

Flow Velocity

0

linear

Volume Flow

1

linear

Mass Flow

2

linear

Temperature

3

linear

Density

4

linear

Sensor Average

5

linear

Diagnostic value, optional, available

when one of the diagnostic channels (1,

2, 3) is set to "Sensor Average".

Sensor Deviation

6

linear

Diagnostic value, optional, available

when one of the diagnostic channels (1,

2, 3) is set to "Sensor Deviation".

Drive Level

7

linear

Diagnostic value, optional, available

when one of the diagnostic channels (1,

2, 3) is set to "Drive Level".

Tube Frequency

8

linear

Diagnostic value, optional, available

when one of the diagnostic channels (1,

2, 3) is set to "Tube Frequency".

9

linear

10

linear

2 Phase Signal

11

linear

Diagnostic value, optional, available

when one of the diagnostic channels (1,

2, 3) is set to "2 Phase Signal".

Concentration 1

12

linear

Available when concentration

measurement is switched on.

Concentration 2

13

linear

Available when concentration

measurement is switched on and

Concentration 2 is not switched off.

.book Page 139 Monday, August 26, 2013 9:05 AM