Description of hart interface, 4 inputs/outputs and hart, Dynamic variables and device variables – KROHNE MFC 400 EN User Manual
Page 139

DESCRIPTION OF HART INTERFACE
9
139
MFC 400
www.krohne.com
08/2013 - 4002075802 - MA MFC 400 R02 en
9.4 Inputs/outputs and HART
®
dynamic variables and device variables
The signal converter is available with various input/output combinations.
The connection of the terminals A…D to the HART
®
dynamic variables PV, SV, TV and 4V depends
on the device version.
PV = Primary Variable; SV = Secondary Variable; TV = Tertiary Variable; 4V = Fourth Variable
The signal converter can provide up to 14 measurement-related values. The measured values
are accessible as so-called HART
®
device variables and can be connected to the HART
®
dynamic
variables. The availability of these variables depends on the device versions and the settings.
Code = device variable code
Device variables
Signal converter version
HART
®
dynamic variable
PV
SV
TV
4V
Basic I/O, connection terminals
A
D
-
-
Modular I/O and Ex i I/O, connection terminals
C
D
A
B
HART
®
device variable
Code
Type
Explanations
Flow Velocity
0
linear
Volume Flow
1
linear
Mass Flow
2
linear
Temperature
3
linear
Density
4
linear
Sensor Average
5
linear
Diagnostic value, optional, available
when one of the diagnostic channels (1,
2, 3) is set to "Sensor Average".
Sensor Deviation
6
linear
Diagnostic value, optional, available
when one of the diagnostic channels (1,
2, 3) is set to "Sensor Deviation".
Drive Level
7
linear
Diagnostic value, optional, available
when one of the diagnostic channels (1,
2, 3) is set to "Drive Level".
Tube Frequency
8
linear
Diagnostic value, optional, available
when one of the diagnostic channels (1,
2, 3) is set to "Tube Frequency".
9
linear
10
linear
2 Phase Signal
11
linear
Diagnostic value, optional, available
when one of the diagnostic channels (1,
2, 3) is set to "2 Phase Signal".
Concentration 1
12
linear
Available when concentration
measurement is switched on.
Concentration 2
13
linear
Available when concentration
measurement is switched on and
Concentration 2 is not switched off.
.book Page 139 Monday, August 26, 2013 9:05 AM