Operation, 4 function tables – KROHNE MFC 400 EN User Manual
Page 68
6
OPERATION
68
MFC 400
www.krohne.com
08/2013 - 4002075802 - MA MFC 400 R02 en
6.4 Function tables
6.4.1 Menu A, Quick Setup
INFORMATION!
•
The following tables describe the functions of the standard device with HART
®
connection.
The functions for Modbus, Foundation Fieldbus and Profibus are described in detail in the
corresponding supplementary instructions.
•
Depending on the device version, not all functions are available.
No.
Function
Setting / Description
A1 Language
A1
Language
Language selection depends on the device version.
A2 Tag
A2
Tag
Measuring point identifier (Tag no.) (also for HART
®
operation) appears in
the LCD header (max. 8 digits).
A3 Reset
A3
Reset
A3.1
Reset Errors
Reset Errors? Select: No / Yes
A3.2
All Totalisers
Reset Totaliser? Select: No / Yes (available if activated in C6.9.4)
A3.3
Totaliser 1
Reset Totaliser? Select: No / Yes (available if activated in C6.9.4)
A3.4
Totaliser 2
Reset Totaliser? Select: No / Yes (available if activated in C6.9.4)
A3.5
Totaliser 3
Reset Totaliser? Select: No / Yes (available if activated in C6.9.4)
A4 Analogue Outputs (only for HART
®
)
A4
Analogue Outputs
Applicable to all current outputs (terminals A, B and C), frequency outputs
(terminals A, B and D), limit switch (terminals A, B, C, and / or D) and the 1st
display page / line 1.
A4.1
Measurement
Select:
Volume Flow / Mass Flow / Temperature / Density / Velocity / Sensor
Average / Sensor Deviation / Drive Level / Tube Frequency / Strain 1 /
Strain 2 / 2 Phase Signal
Depending on the settings for the concentration measurement, the following
measurements are possible:
Concentration 1 / Concentration 2 / Conc. mass flow 1 / Conc. mass flow 2 /
Conc. volume flow 1 / Conc. volume flow 2
Use for all outputs? (also use this setting for Fct. A4.2...A4.5!)
Setting: no (applies only to the main current output ) / yes (applies to all
analogue outputs)
A4.2
Unit
Selection of the unit from a list, depending on the "measurement"
A4.3
Range
Setting for main current output (range: 0...100%)
Setting: 0…x.xx (format and unit, depending on measurement, see A4.1 and
A4.2 above)
Use for all outputs? Make setting, see Fct. A4.1 above!
A4.4
Low Flow Cutoff
1) Setting for main current output (sets output value to "0")
Setting: x.xxx ± x.xxx% (range: 0.0…20%)
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
2) Use for all outputs? Make setting, see Fct. A4.1 above!