OPERATION

6

75

MFC 400

www.krohne.com

08/2013 - 4002075802 - MA MFC 400 R02 en

C3._.7

Polarity

Set polarity; the flow direction in C1.3.2 must be noted!

Select:

Both Polarities (plus and minus values are displayed) /

Positive Polarity (display for negative values = 0) /

Negative Polarity (display for positive values = 0) /

Absolute Value (always displays positive, with both negative and positive

values)

C3._.8

Limitation

Limitation before applying the time constant

±

xxx … ±xxx%; range: -150…+150%

C3._.9

Low Flow Cutoff

Sets the measurement to "0" for low values

x.xxx ± x.xxx%; range: 0.0…20%

(1st value = switching point / 2nd value = hysteresis),

condition: 2nd value ≤ 1st value

C3._.10

Time Constant

Range: 000.1…100 s

C3._.11

Special Function

Automatic Range;

Select:

Off (switched off) /

Automatic Range (range is changed automatically, extended lower range,

only makes sense in combination with a status output) /

External Range (change by control input, extended lower range; control

input must also be activated)

C3._.12

Threshold

Appears only when Fct. C3._.11 "Threshold" is activated between extended

and normal range. The automatic range function always changes from the

extended to the normal range when the 100% current is reached.

The upper 100% value of the hysteresis is then = 0. The threshold is then the

hysteresis value, instead of "Threshold ± Hysteresis" as shown in the

display.

Range: 5.0…80%

(1st value = switching point / 2nd value = hysteresis),

condition: 2nd value ≤ 1st value

C3._.13

Information

Serial no. of the I/O board, software version no. and production date of the

circuit board

C3._.14

Simulation

Sequence see B1._ current output X

C3._.15

4mA Trimming

Trimming of the current at 4 mA

Reset to 4 mA restores the factory calibration.

Used for HART

®

setting.

C3._.16

20mA Trimming

Trimming of the current at 20 mA

Reset to 20 mA restores the factory calibration.

Used for HART

®

setting.