background image

4

ELECTRICAL CONNECTIONS

28

MFC 400

www.krohne.com

08/2013 - 4002075802 - MA MFC 400 R02 en

4.7.2 Description of the CG number

The last 3 digits of the CG number (5, 6 and 7) indicate the assignment of the terminal
connections. Please refer to the following examples.

Examples for CG number

Description of abbreviations and CG identifier for possible optional modules
on terminals A and B

Figure 4-3: Marking (CG number) of the electronics module and input/output variants

1 ID number: 3
2 ID number: 0 = standard; 9 = special
3 Power supply option
4 Display (language versions)
5 Input/output version (I/O)
6 1st optional module for connection terminal A
7 2nd optional module for connection terminal B

CG 330 11 100

100...230 VAC & standard display; basic I/O: I

a

or I

p

& S

p

/C

p

& S

p

& P

p

/S

p

CG 330 11 7FK

100...230 VAC & standard display; modular I/O: I

a

& P

N

/S

N

and optional module P

N

/S

N

& C

N

CG 330 81 4EB

24 VDC & standard display; modular I/O: I

a

& P

a

/S

a

and optional module P

p

/S

p

& I

p

Abbreviation

Identifier for CG No.

Description

I

a

A

Active current output

I

p

B

Passive current output

P

a

/ S

a

C

Active pulse output, frequency output, status output or limit switch

(changeable)

P

p

/ S

p

E

Passive pulse output, frequency output, status output or limit switch

(changeable)

P

N

/ S

N

F

Passive pulse output, frequency output, status output or limit switch acc.

to NAMUR (changeable)

C

a

G

Active control input

C

p

K

Passive control input

C

N

H

Active control input to NAMUR

Signal converter monitors cable breaks and short circuits acc. to

EN 60947-5-6. Errors indicated on LC display. Error messages possible

via status output.

-

8

No additional module installed

-

0

No further module possible

.book Page 28 Monday, August 26, 2013 9:05 AM