ELECTRICAL CONNECTIONS

4

41

MFC 400

www.krohne.com

08/2013 - 4002075802 - MA MFC 400 R02 en

Pulse/frequency output passive, basic I/Os

• U

ext

≤ 32 VDC

• f

max

in the operating menu set to f

max

≤ 100 Hz:

I ≤ 100 mA
open:
I ≤ 0.05 mA at U

ext

= 32 VDC

closed:
U

0, max

= 0.2 V at I ≤ 10 mA

U

0, max

= 2 V at I ≤ 100 mA

• f

max

in operating menu set to 100 Hz < f

max

≤ 10 kHz:

I ≤ 20 mA
open:
I ≤ 0.05 mA at U

ext

= 32 VDC

closed:
U

0, max

= 1.5 V at I ≤ 1 mA

U

0, max

= 2.5 V at I ≤ 10 mA

U

0, max

= 5.0 V at I ≤ 20 mA

• If the following maximum load impedance R

L, max

is exceeded, the load impedance R

L

must

be reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R

L, max

= 47 kΩ

f ≤ 1 kHz: R

L, max

= 10 kΩ

f ≤ 10 kHz: R

L, max

= 1 kΩ

• The minimum load impedance R

L, min

is calculated as follows:

R

L, min

= (U

ext

- U

0

) / I

max

• Can also be set as a status output; for the electrical connection refer to status output

connection diagram.

INFORMATION!

Compact and field housing versions:

Compact and field housing versions:

Compact and field housing versions:

Compact and field housing versions: Shield connected via the cable terminals in the terminal
compartment.

Any connection polarity.