<15. OPERATION OF SENCOM pH/ORP>
15-2
IM 12A01A02-01E
5th Edition : Oct. 31, 2013-00
15.1 Change language
The screen is set to display English at factory shipment; if you wish to use the FLXA21 in another
language, first select a language as described in section 2.7.
15.2 Quick setup
The Quick setup screen is used to set up the basic items you want to set up first, such as the
date/time and sensor settings. The detailed settings are described in chapter 16, Commissioning.
You may leave the Quick setup now and return to it later; however, it is recommended to perform
the quick setup first.
Each time the FLXA21 is started up, this screen is displayed. If it is not necessary to change the
setup, press No or
.
NOTE
When no operation is performed for 10 minutes or 60 minutes (depending on the setting of “Auto
Return”), the display except Trend display automatically changes to the Monitor display (or to the
Main display when the MONITOR display is disabled).
NOTE
The display may show “---- (bar)” when starting measurement, which means the sensor is not
ready to measure. But the temperature is displayed normally. Wait until measurement values are
displayed.
While a bar (----) is displayed, as for the mA output, in the case of “Off” or “Low,” [Burn] of the
Output setup (see section 16.3) is fixed 3.6mA, and, in the case of “High,” 22.0mA becomes
fixed.