Table C4-1 List of power cables
Cable
Dimensions (mm)
Phoenix
Contact's type
Section
area
(mm
2
)
AWG
Strip
length
(mm)
I
1
I
2
d
1
S
1
d
2
S
2
0.25
24
10
10.5
6.0
0.8
0.15
2.0
0.25
AI 0.25-6 BU
0.34
22
10
10.5
6.0
0.8
0.15
2.0
0.25
AI 0.34-6 TQ
10
12.5
8.0
0.8
0.15
2.0
0.25
AI 0.34-8 TQ
0.5
20
10
12.0
6.0
1.1
0.15
2.5
0.25
AI 0.5-6 WH
10
14.0
8.0
1.1
0.15
2.5
0.25
AI 0.5-8 WH
10
16.0
10.0
1.1
0.15
2.5
0.25
AI 0.5-10 WH
0.75
20
10
12.0
6.0
1.3
0.15
2.8
0.25
AI 0.75-6 GY
10
14.0
8.0
1.3
0.15
2.8
0.25
AI 0.75-8 GY
10
16.0
10.0
1.3
0.15
2.8
0.25
AI 0.75-10 GY
1.0
18
10
12.0
6.0
1.5
0.15
3.0
0.3
AI 1-6 RD
10
14.0
8.0
1.5
0.15
3.0
0.3
AI 1-8 RD
10
16.0
10.0
1.5
0.15
3.0
0.3
AI 1-10 RD
1.5
16
10
12.0
6.0
1.8
0.15
3.4
0.3
AI 1.5-6 BK
10
14.0
8.0
1.8
0.15
3.4
0.3
AI 1.5-8 BK
10
18.0
10.0
1.8
0.15
3.4
0.3
AI 1.5-10 BK
2.5
14
10
14.0
8.0
2.3
0.15
4.2
0.3
AI 2.5-8 BU
10
16.0
10.0
2.3
0.15
4.2
0.3
AI 2.5-10 BU
IMPORTANT
• Use the same manufacturer for sleeves and tools.
• Use sleeve tools that match the wire thickness.
• Insert the wire to be connected completely into the pressure clamp terminal and attach it
securely.
• Secure the cable to cable clamps, etc. so that the weight of the cable applied to the terminal
is minimized.
• Strip the cable for a length so that the core wire slightly extends from the metal tube of the
sleeve. If this causes the length of the metal tube of the sleeve to be slightly shorter than the
stripping length, this is no problem.