Temperature Range:

Operating: -40 to +65°C (altitude : up to 2000m)

-40 to +55°C (altitude : more than

2000m, up to 3000m)

Storage: -40 to +85°C

Humidity Range:

Operating: 5 to 95 %RH (non-condensation)

Storage: 5 to 95 %RH (non-condensation)

Temperature Gradient:

Operating: ±10°C/h or less

Storage: ±20°C/h or less

Power Supply:

Voltage Range : 10.8~26.4 V DC

Rated Power Supply : 24 V DC

Momentary Power Failure : Instant

Disconnection

DC Power Supply Ripple Ratio : 1%

p-p

or less

Power Consumption:

Max. 10 W

Degrees of Protection:

IP20

Vibration Resistance:

0.15 mm P-P (5~58 Hz) , 1 G (58~150 Hz)

Shock Resistance:

15 G 11 ms

Noise Resistance:

Electric Field : 3 V/m or less (80MHz~1GHz)

Electrostatic Discharges: 4 kV or less (contact

discharge), 8 kV or less (aerial discharge)

Grounding:

Class-D grounding (no sharing ground with

others)

Cooling:

Natural Air Cooling

n

Regulatory Compliance State-

ments

EMC Conformity Standards:

EN61326-1 Class A, Table 2 (for use in industrial

locations), EN55011 Class A group1, EN61000-

6-2

Safety Requirements:

EN61010-1, CSA C22.2 No. 61010-1

Indoor use only

Explosion-Proof Types:

FM, ATEX, CSA, IECEx (approvals under

pending)

n

Physical Specifications

Housing Material:

Aluminum alloy plate with polyester, mint-green

paint (Munsell 5.6BG 3.3/2.9 or its equivalent)

External Dimension:

150 x 60 x 140 mm (not include projection)

Weight:

Approx. 1.0 kg

Mounting:

DIN RAIL Mounting