D4-39, Important – Yokogawa YFGW410 User Manual
Page 176

D4-39
IM 01W02D01-01EN
The time required for update depends on the device type. Target values for time taken are as fol-
lows.
Firmware
Time required for
downloading (min.) *1
Assumptions
YFGW410
8 min./device
YFGW510
3 min./device
Field wireless
device
Radio
15 min./device
For EJX-B series, YTA510, and YTMX580.
60 min./30 devices
Sensor
360 min./device
For EJX-B series, YTA510, and YTMX580.
360 min./25 devices
*1
Not including the time taken from firmware application to restart
IMPORTANT
During radio firmware download, the publish data may be interrupted.
IMPORTANT
It is not possible to update radio firmware, sensor firmware, and backbone device firmware simul-
taneously. Carry out the download and apply for each firmwware.
When applying a new firmware, refer the procedure in the each firmware release note.
IMPORTANT
Firmware downloads for field wireless devices can be carried out for a maximum of 100 devices
simultaneously.
IMPORTANT
By Applying a firmware, devices will restart automatically. Care should be taken because restart-
ing a device having a relay function within the field wireless network may affect all connected
devices below this device in the hierarchy.
There are ISA100.11a field wireless devices provided by other manufacturers which do not auto-
matically restart after applying a firmware. In this case, restart devices manually. For the method
of manually restarting, see “Select Restart Devices” in this sub-section.
IMPORTANT
Even if the Firmware Download Manager is closed, the firmware update process is running in
background. However if the Monitor is closed, all status of firmware update will be cleared. So
do not close the Monitor before not completing firmware update process. A firmware download
may take a considerable time, so it requires to care when closing the window during a firmware
download to carry out another operation, until the firmware update process is completed.