When the [OK] button is clicked, the automatic allocation is reflected in the Input Registers tab.
When the [Cancel] button is clicked, the information is not changed and the dialog is closed.
The order of the auto mapping follows rules in the chart.
Parameter
Normal Mapping
Data Type Mapping
GW_STATUS (YFGW410)
0 to 8 (Reserve 9 to 29)
0 to 7 (Reserve 8 to 29)
BBR_STATUS
30 to 389 (Reserve 390 to 499)
30 to 349 (Reserve 350 to 499)
Publish data and DEV_STATUS
500~65535
500 to (Start of status setting -1)
All parameter allocation information can be deleted by clicking the [Clear All] button. When the
[Clear All] button is clicked, the dialog shown in Figure D3-63 appears.
FD0369.ai
Figure D3-63 Modbus Registers Settings Deletion Warning Dialog
When the [OK] button is clicked, the information is deleted. When the [Cancel] button is clicked,
the information is not deleted and the dialog is closed.
Filter settings
The display range of the [Input Registers] section can be limited by filter settings.
In the Start Address field, enter the register number from which to start display. In the End Ad-
dress field, enter the register number from which to end display.
Clicking the [Enable Filter] button enables the filter settings and limits the register numbers that
are displayed. Clicking the [Disable Filter] button disables the filter settings and all register num-
bers are displayed.