E1. Routine Maintenance
For the field wireless network, it is important to monitor the degree of stability communications
after the setup task was completed and the system started normal operations. A wireless com-
munication may become unstable due to the influence of obstacles on radio waves on the com-
munication path. Particular care is required to extend a new building or equipment, temporarily
install a metallic structure for construction or maintenance work, or use construction equipments.
E1.1 Routine Maintenance
E1.1.1 Operation Status of Wireless System
For routine maintenance, start the Monitor on the Field Wireless Management Console through a
PC connected to the YFGW410 in order to monitor the status of the wireless system.
When placing a PC for starting the Monitor near the YFGW410 to take tasks, connect it to the
maintenance interface of the YFGW410. When working in secured room or other place in which
host applications are running, connect the PC registered in the access control list to the field
network interface.
For routine maintenance, check by the Monitor that the status information of YFGW410,
YFGW510 and field wireless devices are normal.
For details on how to check the status of the wireless system on the Monitor, see Chapter D4
Starting up the Field Wireless System.
E1.1.2 YFGW410 Maintenance
For YFGW410 maintenance, check the device installation status as well as the operation status
of wireless system components.
Check device installation, power supply cable, cable connection and stain condition.
If the YFGW410 becomes dirty or dusty, wipe with a soft cloth moistened with water or mild soap.
IMPORTANT
The housing has an open ventilation hole for heat radiation. When wiping out, be sure not to al-
low any foreign matter or water to get inside.
IMPORTANT
For details on how to check YFGW510, field wireless device, and other components, see the
user’s manual of the relevant devices.