Part g specifications, G1. yfgw410, G1.1 standard specification – Yokogawa YFGW410 User Manual
Page 190: G1.1, Part g specifications g1. yfgw410, G1-1, Ncommunication interface

G1-1
IM 01W02D01-01EN
Part G Specifications
G1. YFGW410
G1.1 Standard Specification
n
Communication Interface
Item
Field Network Specifications
Field Wireless
Backbone
Specifications
Maintenance/Diagnostic
Network Specifications
Communication
Interface
Standard
100BASE-TX
*2
RS-485
100BASE-TX
*2
100BASE-TX
*4
RS-232C
*4 *5
Transmission
Speed
100Mbps
38.4Kbps
100Mbps
100Mbps
115.2kbps
Connector
RJ-45
Proprietary
RJ-45
RJ-45
RJ-11
Cable Type
Category 5
AWG24~12
Category 5
Category 5
Proprietary
Maximum
Length
100m
1200m
100m
100m
15m
Number of
Ports
3 ports
1 port
4 ports
1 port
1 port
Port Name
F1, F2, F3
–
B1, B2, B3, B4
M1
–
Protection
Surge
Isolated, Surge
Surge
–
–
Communication
Protocol
Modbus
Modbus/TCP
Modbus/RTU
–
–
–
OPC
*1
Proprietary
*3
–
–
–
–
Management,
configuration,
etc.
HTTP
NTP/SNTP
Proprietary
*3
–
HTTP
IEEE1588PTP v2
Proprietary
*3
HTTP
Proprietary
*3
–
*1:
OPC interface connection is available by Field Wireless Device OPC Server (SSS7100). For details of this product, see related
products General Specifications.
*2:
In outdoor wiring to Field Network or 100BASE-TX of Field Wireless Backbone, use optical fiber cables with a nonmetallic ten-
sion member, combining with YFGW610.
*3:
TCP based custom protocol used for communication between this product, “Field Wireless OPC Server”, “FieldMate Versatile
Device Management Wizard”, “Plant Resource Manager (PRM)”, and YFGW510. For details of each product, see related prod-
ucts General Specifications.
*4:
Maintenance/Diagnostic Network (100BASE-TX, RS-232C) are not available for outdoor wiring.
*5:
These are the serial ports for a maintenance which only our company use.
n
OPTIONAL SPECIFICATIONS (For Explosion Protected Types)
Item
Specification
Code
Factory Mutual (FM)
Nonincendive Approval
*1
–
ATEX
Type n Declaration
*2
–
Canadian Standards Association (CSA)
Nonincendive Approval
*1
–
IECEx
Type n Approval
*2
–
*1:
To be compliant with these standards, the YFGW410 hardware needs to be installed in a lockable metal cabinet.
*2: To be compliant with these standards, the YFGW410 hardware needs to be installed in a lockable metal cabinet of IP54 or higher
protection rating.