D3-48, Adding sampling data – Yokogawa YFGW410 User Manual
Page 109

D3-48
IM 01W02D01-01EN
Adding sampling data
When the [Add] button in Figure D3-48 is clicked, the window shown in Figure D3-49 appears.
FD0349.ai
Figure D3-49 Sampling Settings Window
Item
Description
Initial
settings
Device Tag
Device tag name of the device whose information is displayed in
this window.
Blank when
new items are
added
CF/DD
CF File
Name of the CF file associated with the displayed device.
DEV_REV
This is the device revision.
CFREV
This is the CF file revision.
DD File
This function is not used.
The Sampling Settings window has two tabs, which can be viewed by selecting the [Read Pa-
rameters] and [Write Parameters] tabs.
At the [Read Parameters] tab, configure the parameters to transmit data from the selected field
wireless device to the host system. At the [Write Parameters] tab, configure the parameters to
transmit data from the host system to the selected field wireless device.
• Registering and Deleting Capabilities Files
CF files contain the following data: vendor names, model names, revisions, embedded
process data (flow rate, temperature, pressure, and other measurement values) and device
self-diagnosis information. This information is provided by the device vender. Therefore, it is
necessary to acquire the CF file for the relevant model before registration.
First, register the CF file of the model to register sampling data.
When the [CF File] drop-down box is clicked, the default drop-down box is displayed, as
shown in Figure D3-50.