4.3 Building of SIO communication network (SIO communication)

4.3.1 Wiring

(1) Basic

Item Contents

Number of connecting units

16 axes max. (Depends on the operation mode. Refer to “1.4 Features”)

Communication cable length

Total cable length 100m or shorter

Communication cable

Two-paired twisted pair shielded cable

Terminal resistor

Recommended cable: Taiyo Electric Wire & Cable


CAUTION

1. Provide a communication path via a bus connection, and be sure to connect a terminal resistor at the

end. A terminal resistor is incorporated into the gateway unit side, therefore, it is unnecessary to connect
it.

2. The communication cable should be supplied by customer. If the recommended communication cable

is not used, use an electric wire size AWG22.


(2) Link connection for PCON-SE, ACON-SE


Gateway unit

(Incorporating

terminal resistor)

e-CON connector (AMP made 4-1473562-4: Green)
e-CON connector (AMP made 3-1473562-4: Orange)

Junction (AMP made 3-1473574-4:)

Recommended brand HK-SB/20276 × L 2P ×
AWG22

SIO communication

main line

First axis

Second axis

n

th

axis

Controller link cable
CB-RCB-CTL002

Terminal resistor
R=220Ω
1/4W