Page 129

background image

125

CC-Link communication status indication list


: Lit ●: Unlit ◎: Flashing

RUN

(Green)

ERR

(Red)

SD

(Green)

RD

(Green)

Operation

Communication is normally performed, however, CRC(*) error
frequently occurs due to noise.

0.4s◎

Baud rate or station No. has changed from baud rate for reset
release or station No. setting.

(Impossible status)

Received data became CRC(*) error, and cannot respond.

(Impossible status)

Normal communication

(Impossible status)

No data is transmitted to local station.

(Impossible status)

Polling response is performed, but refresh reception is CRC(*) error.

(Impossible status)

Data to local station is CRC(*) error

(Impossible status)

Not link-started.

(Impossible status)

There is no data to local station, or reception for local station is
impossible due to noise.

Data cannot be received due to disconnection. Power is shut off or
H/W is being set.

Invalid baud rate, invalid station No. setting

Invalid baud rate, invalid station No. setting

Power is shut off, or remote station power part is in fault.


*CRC: Cyclic Redundancy Check

Data error detecting method which is mostly used for synchronizing transmission