Section 5: Commissioning

05/11 61

51209 Revision 2

5.8.1

Adapting the Analog Output

The output current can be adapted in small ranges. This is required, if small deviations from the
nominal value occur in a connected PLC.
Open the menu with

[Show HW-slots]-[Slot 1/2 PR5510/07 analog I/O]:

Info/HW-Slots

Builtin

RS 232

Slot 1

PR 5510/0
4

analog I/O

PR 5510/07 is fitted in Slot 1

Slot 2

-empty-

Slot 3

Builtin

Digital I/O

Slot 4

Profibus-DP


Select [PR 5510/07 analog I/O] and confirm with

Info/HW-Slots

PR5510/07 on slot

1

In use by PLC task

2

Analog output

0.0000 mA Select with

Stop PLC Stop I/O

Adjust

Reset

Press [Adjust]



Adapt analog output ?


Safety prompt: Reply [Yes] to start adapting.


Info/HW-Slots/Adjust Analog Output Slot 1

Output

4.000 mA

Measured

4.004 mA


Enter e.g. the value for 4 mA measured by the connected PLC under [Measured].
After pressing

, the 2nd value (20 mA) is displayed:

Info/HW-Slots/Adjust Analog Output Slot 1

Output

20.000 mA

Measured

20.010 mA


Enter e.g. the value for 20 mA measured by the connected PLC under [Measured].

Save settings ?

Reply [Yes] to save the data,
or [No] to keep the previous values.


If you want to return to the factory settings (4 mA and 20 mA):
Press [Reset]: A safety prompt is displayed:

Reset to default ?

Reply [Yes] for reset to the factory settings, or
[No], if you want to keep the entered values unchanged.