Section 3: Installing the Instrument

05/11 23

51209 Revision 2

3.2.9

3 Optocoupler Inputs


The optocoupler inputs have one common potential (GND) for the input group that is separated
from the common potential of the output group.

Connection method: 4-pin plug-in terminal block
Cable:

Shielded, max. 50 m

Number of outputs: 3
Input signal:

External supply required
10 ... 28 V DC for 'high' level
0 ... 5 V DC for 'low' level

Input voltage:

Max. 28 V DC

Input current:

< 11 mA @ 24 V DC
< 5 mA @ 12 V DC

Electrical isolation:

Yes; a common minus potential for the
group of 3 inputs


Example: contact input connection

When a voltage >= 10 VDC is applied to the terminals (in
the example :1-GND), input 1 is active (true).