Fairbanks X SERIES PR 5220 ETHERNET TRANSMITTER User Manual
Page 22

Section 3: Installing the Instrument
05/11 23
51209 Revision 2
3.2.9
3 Optocoupler Inputs
 
The optocoupler inputs have one common potential (GND) for the input group that is separated 
from the common potential of the output group. 
 
Connection method: 4-pin plug-in terminal block 
Cable: 
Shielded, max. 50 m
Number of outputs: 3 
Input signal: 
External supply required 
10 ... 28 V DC for 'high' level 
0 ... 5 V DC for 'low' level 
Input voltage:
Max. 28 V DC
Input current:
< 11 mA @ 24 V DC 
< 5 mA @ 12 V DC 
Electrical isolation:
Yes; a common minus potential for the 
group of 3 inputs 
 
Example: contact input connection 
 
When a voltage >= 10 VDC is applied to the terminals (in 
the example :1-GND), input 1 is active (true). 