Fairbanks X SERIES PR 5220 ETHERNET TRANSMITTER User Manual
Page 54
Section 5: Commissioning
05/11 55
51209 Revision 2
5.7.2
Configuring Digital Inputs and Outputs
Under
-[Digital I/O parameter], you can open the configuration menu for outputs and inputs:
Setup/Digital I/O parameter
Output 1
marker bit 1
X64=1
Output 2
marker bit 2
X65=1
Output 3
marker bit 3
X66=1
Input 1 on
-no action-
Input 1 off
-no action-
Input 2 on
-no action-
Input 2 off
-no action-
Input 3 on
-no action-
Input 3 off
-no action-
5.7.3
Configuring Outputs
Configure the required function for [Output 1] to [Output 3] by selecting a signal from the list; see
Chapter 5.7.1. The output goes to the corresponding state.
Example:
Setup/Digital I/O parameter
Output 1
below zero
X35=1
Output 2
above Max
X33=0
Output 3
center zero
X36=1
Input 1 on
-no action-
[Output 1] is true (active), when the weight value drops below zero (X35=1).
[Output 2] remains (active), as long as the weight is not above Max (X33=0).
[Output 3] is true (active), when the weight is zero +/- 1/4 d (X36=1).