Section 3: Installing the Instrument
05/11 25
51209 Revision 2
3.2.11 Profibus Interface (PR 5220/01 only)
Communication protocols and syntax comply with the Profibus-DP standard to IEC 61158 with 
transfer rates up to 12 Mbit/s. 
 
Transfer rate:
9.6 kbit/s to 12 Mbit/s, 
baud rate auto-detection 
Protocol:
PROFIBUS-DP-V0 slave 
to EN 50 170 (DIN 19245), 
mono or multi-master systems are 
supported. Master and slave 
devices, max. 126 nodes possible. 
Watchdog timer 
Transport:
EIA RS-485 , Profibus DIN 19245 
Part 1 
Cable:
Profibus special colour: violet 
Shielded twisted pair cable 
Cable impedance: 150 ohms 
Certificates: 
Profibus test center Comdec in 
Germany and PNO (Profibus User 
Organization). 
Suitable for industrial applications to 
CE, UL and cUL 
Electrical isolation: Optocoupler in lines A and B (RS-
485)
Cable length:
Max. distances 200m can be 
extended with 1.5 Mbit/s by means 
of additional repeater 
 
Connection to the Profibus is using the 9-contact plug-in socket on the front panel. 
The transmitter is the only or last slave on
the bus
The transmitter is not the only or
last slave on the bus
PIN
Signal
3 
4 
5 
6 
8 
RxD/TxD-
P
CNTR-P
DGND
VP
RxD/TxD-
P