beautypg.com

Micromod MOD: 30ML Functions Data Base Reference User Manual

Page 91

background image

MOD 30ML Data Base Reference

BUILT-IN ANALOG OUTPUT BLOCK


07

Active I/O communications Error (COMMERRA)........................................................... – – R
If the I/O communications error diagnostic is enabled, this active diagnostic status
indicates if the error is active even after acknowledgement. The status can be read
as follows.

YES

1

Diagnostic error is active.

NO

0

Diagnostic error is not active.


08

OUTPUT Error (OUTERRS) .............................................................................................. CWR
The analog output error diagnostic is a status indication for the output circuit error
code (see attribute #12). The diagnostic can be suppressed or enabled as follows.

SUPPRESS

1

Diagnostic error is suppressed. Acknowledgement status remains
clear.

ENABLE

0

Diagnostic error is not suppressed and errors are reported to the
System Event block.


09

Unacked Output Error (OUTERRU) .................................................................................– WR
If the analog output diagnostic error is enabled, this unacknowledged status
indicates if the diagnostic is or is not acknowledged. The status can be
acknowledged or read as follows.

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.


10

Active Output Error (OUTERRA) ..................................................................................... – – R
If the analog output diagnostic error is enabled, the active status indicates if the
error is active even after acknowledgement. The status can be read as follows.

YES

1

Diagnostic error is active.

NO

0

Diagnostic error is not active.


11

Output Number (OUTNUM) .............................................................................................. CWR
The analog output number.

1

The analog output is connected to Output 1 of the built-in circuit.

2

The analog output is connected to Output 2 of the built-in circuit.


12

Output Circuit Error (ERROR) .........................................................................................– WR
This error code indicates the reason for report of an Output Error diagnostic
(attribute #08).

0 No

error

1

Output too low

2

Output too high

2-83