beautypg.com

Built-in analog input block parameters – Micromod MOD: 30ML Functions Data Base Reference User Manual

Page 73

background image

MOD 30ML Functions

BUILT-IN ANALOG INPUT BLOCK

Figure 2-26 Built-In Analog Input Block (AIN), Edit Display


2.7.2

Built-in Analog Input Block Parameters

The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 2-9. A description of
each attribute is provided in the attribute list that follows the table.

Table 2-9. Built-In Analog Input Block Attributes, Valid Values, Mnemonics, and Data Types

Field Name / Attribute

Mnemonic Valid Values

CWR Data Type

Attr

Version

VERSION 1

– – R Long State

00

Block Length

BLKLEN

– – R Count

01

Block State

STATE

RUN (0)

– – R Short State

02

Bad Inputs Accepted

BADINP

YES (1)

– – R Discrete

03

Diagnostics Group

SUPPGRP NONE, 1 to 7

CWR Long State

04

I/O communications error

COMMERRS

ENABLE (0), SUPPRESS (1)

CWR Discrete

05

Unacked comm. error

COMMERR
U

NO (0), YES (1)

– WR Discrete

06

Active comm. error

COMMERRA

NO (0), YES (1)

– – R Discrete

07

Input Error

INERRS

ENABLE (0), SUPPRESS (1)

CWR Discrete

08

Unacked

Input Error

INERRU

NO (0), YES (1)

– WR Discrete

09

Active

Input Error

INERRA

NO (0), YES (1)

– – R Discrete

10

Input Number

INNUM

1, 2

C – R Long State

11

Error

ERROR

– WR Short State

12

2-65