MOD 30ML Functions

DISPLAY INTERFACE BLOCK

Display Interface Block Page 2
Use this page to set values for timeouts and passwords.

Figure 2-10. Display Interface Block (DIF), Edit Display, page 2

Password timeout (minutes) (See attribute 17 description.)
The time in minutes (1 - 54) that the tune and configure access levels will timeout and return
to the operator level after last keyboard activity. No timeout = Current access level will not
timeout and change.

Entry timeout (50 millisecond ticks) (See attribute 38 description.)
Number of seconds before an entry activity (ENT flashing) will time out and return to the
previous state after last keyboard entry change. No timeout = Entry time out disabled and
ENT will continue to flash until the TAG key is pressed.

Tune password
NONE (0), 1 - 65535. Enter numeric characters ranging from 1 to 65535 to get a tune
password. The password is used by the instrument to get to the tuning displays.

Configuration password
NONE (0), 1 - 65535. Enter numeric characters ranging from 1 to 65535 to get a
configuration password. The password is used by the instrument to get to the configuration
displays.

2-34