MOD 30ML Functions

DISPLAY INTERFACE BLOCK

Display List
Access to different displays in the display list is controlled locally through the TAG key or
remotely from a count variable input. When a remote display number is present and the value
is less than or equal the number of displays in the list, front face navigation using the TAG
key is disabled and the remote input selects the display.

2.3.2

Display Interface Block Parameters

The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 2-3. A description of each
attribute is provided in the attribute list which follows the table.

Table 2-3. Display Interface Block Attributes, Valid Values, Mnemonics and Data Types

Field

Mnemonic

Valid Values

CWR

Data Type

Attr

Version VERSION

1

– –

R Long State

00

Block Length BLKLEN

– –

R Count

01

State

STATE

RUN (0)

– –

R Short State

02

Bad Inputs

BADINP

Rejected (0), Accepted (1)

CWR Discrete

03

DIAGNOSTICS: Group

SUPPGRP NONE, 1 - 7

CWR Long State

04

Faceplate Comm Error

FPCOMS

Enabled (0), Suppressed (1).

CWR Discrete

05

Faceplate Communication error
unacknowledged

FPCOMU NO (0), YES (1).

– WR Discrete

06

Faceplate Communication error
active

FPCOMA

NO (0), YES (1).

R Discrete

07

No Keyboard Response

NOKBDS

Enabled (0), Suppressed (1).

CWR Discrete

08

No Keybrd Response
unacknowledged

NOKBDU

NO (0), YES (1).

– WR Discrete

09

No Keybrd Response active

NOKBDA

NO (0), YES (1).

R Discrete

10

reserved

11

Faceplate Version

FPVER

0.0 - 25.5.

– – R Long State

12

Device Tag

DEVTAG

CWR Ascii

13

Power Up Display User Tag

PUPDISP DEVICE (0), PREVIOUS (65535)

or display tag

CWR Count

14

Current Display

CURDISP

– – R Count

15

Current Access Level

CURACCS OPERATE (0), TUNE (1),

CONFIGURE (2).

– – R Short State

16

Access Timeout

ACCTIME NONE (0), 1 - 54 minutes.

C – – Long State

17

Min Low Alarm Priority

MINLOPRI 2 - 255.

C – R Long State

18

Diagnostics: Display Flash

FLSHDIAG NO (0), YES (1). CWR

Discrete

19

Diagnostics: Beep

BEEPDIAG NO (0), YES (1).

CWR Discrete

20

Diagnostics: Flash/ Beep Rate DFLSHRAT SLOW (0), FAST (1).

CWR Discrete

21

High Priority Process Alarms:
Display Flash

FLSHHIPR NO (0), YES (1).

CWR Discrete

22

High Priority Process Alarms:
Beep

BEEPHIPR NO (0), YES (1).

CWR Discrete

23

High Priority Process Alarms:
Flash/Beep Rate

HFLSHRAT SLOW (0), FAST (1).

CWR Discrete

24

Low Priority Process Alarms:
Display Flash

FLSHLOPR NO (0), YES (1).

CWR Discrete

25

Low Priority Process Alarms:
Beep

BEEPLOPR NO (0), YES (1).

CWR Discrete

26

Low Priority Process Alarms:
Flash/Beep Rate

LFLSHRAT SLOW (0), FAST (1).

CWR Discrete

27

Table 2-3. Display Interface Block Attributes, Valid Values, Mnemonics and Data Types (Cont’d)