Display interface block parameters, 2 display interface block parameters – Micromod MOD: 30ML Functions Data Base Reference User Manual
Page 34
MOD 30ML Functions
DISPLAY INTERFACE BLOCK
Display List
Access to different displays in the display list is controlled locally through the TAG key or
remotely from a count variable input. When a remote display number is present and the value
is less than or equal the number of displays in the list, front face navigation using the TAG
key is disabled and the remote input selects the display.
2.3.2
Display Interface Block Parameters
The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 2-3. A description of each
attribute is provided in the attribute list which follows the table.
Table 2-3. Display Interface Block Attributes, Valid Values, Mnemonics and Data Types
Field
Mnemonic
Valid Values
CWR
Data Type
Attr
Version VERSION
1
– –
R Long State
00
Block Length BLKLEN
– –
R Count
01
State
STATE
RUN (0)
– –
R Short State
02
Bad Inputs
BADINP
Rejected (0), Accepted (1)
CWR Discrete
03
DIAGNOSTICS: Group
SUPPGRP NONE, 1 - 7
CWR Long State
04
Faceplate Comm Error
FPCOMS
Enabled (0), Suppressed (1).
CWR Discrete
05
Faceplate Communication error
unacknowledged
FPCOMU NO (0), YES (1).
– WR Discrete
06
Faceplate Communication error
active
FPCOMA
NO (0), YES (1).
–
–
R Discrete
07
No Keyboard Response
NOKBDS
Enabled (0), Suppressed (1).
CWR Discrete
08
No Keybrd Response
unacknowledged
NOKBDU
NO (0), YES (1).
– WR Discrete
09
No Keybrd Response active
NOKBDA
NO (0), YES (1).
–
–
R Discrete
10
reserved
11
Faceplate Version
FPVER
0.0 - 25.5.
– – R Long State
12
Device Tag
DEVTAG
CWR Ascii
13
Power Up Display User Tag
PUPDISP DEVICE (0), PREVIOUS (65535)
or display tag
CWR Count
14
Current Display
CURDISP
– – R Count
15
Current Access Level
CURACCS OPERATE (0), TUNE (1),
CONFIGURE (2).
– – R Short State
16
Access Timeout
ACCTIME NONE (0), 1 - 54 minutes.
C – – Long State
17
Min Low Alarm Priority
MINLOPRI 2 - 255.
C – R Long State
18
Diagnostics: Display Flash
FLSHDIAG NO (0), YES (1). CWR
Discrete
19
Diagnostics: Beep
BEEPDIAG NO (0), YES (1).
CWR Discrete
20
Diagnostics: Flash/ Beep Rate DFLSHRAT SLOW (0), FAST (1).
CWR Discrete
21
High Priority Process Alarms:
Display Flash
FLSHHIPR NO (0), YES (1).
CWR Discrete
22
High Priority Process Alarms:
Beep
BEEPHIPR NO (0), YES (1).
CWR Discrete
23
High Priority Process Alarms:
Flash/Beep Rate
HFLSHRAT SLOW (0), FAST (1).
CWR Discrete
24
Low Priority Process Alarms:
Display Flash
FLSHLOPR NO (0), YES (1).
CWR Discrete
25
Low Priority Process Alarms:
Beep
BEEPLOPR NO (0), YES (1).
CWR Discrete
26
Low Priority Process Alarms:
Flash/Beep Rate
LFLSHRAT SLOW (0), FAST (1).
CWR Discrete
27
Table 2-3. Display Interface Block Attributes, Valid Values, Mnemonics and Data Types (Cont’d)
2-26