beautypg.com

Built-in analog output block parameters – Micromod MOD: 30ML Functions Data Base Reference User Manual

Page 89

background image

MOD 30ML Data Base Reference

BUILT-IN ANALOG OUTPUT BLOCK


2.8.2

Built-In Analog Output Block Parameters

The mnemonics, valid values, and data types for all fields that may be selected for
display and/or be used in making softwiring connections are listed in Table 2-11. A
description of each attribute is provided in the attribute list that follows the table.

Table 2-11. Built-In Analog Output Block Attributes, Valid Values, Mnemonics, and Data Types

Field Name / Attribute

Mnemonic

Valid Values

CWR Data Type

Attr

Version

VERSION

– – R Long State

00

Block Length

BLKLEN

– – R Count

01

State

STATE

RUN (0)

– – R Short State

02

Bad Inputs

BADINP

Rejected (0), Accepted (1)

CWR Discrete

03

Diagnostic Group

SUPPGRP NONE, 1 to 7

CWR Long State

04

I/O communications error

COMMERRS

ENABLE (0), SUPPRESS (1)

CWR Discrete

05

Unacked I/O comm. error

COMMERR
U

NO (0), YES (1)

– WR Discrete

06

Active I/O comm. error

COMMERRA

NO (0), YES (1)

– – R Discrete

07

OUTPUT Error

OUTERRS ENABLE (0), SUPPRESS (1)

CWR Discrete

08

Unacked Output error

OUTERRU NO (0), YES (1)

– WR Discrete

09

Active Output error

OUTERRA NO (0), YES (1)

– – R Discrete

10

Output Number

OUTNUM

1, 2

C – R Long State

11

Output Circuit Error

ERROR

– WR Short State

12

Mode

MODE

MANUAL (0), AUTO (1)

CWR Discrete

13

Action

ACTION

REVERSE (0), DIRECT (1)

CWR Discrete

14

Input Range, Top

INHI

Floating Pt Value, E.U. CWR

Floating

Pt

15

Input Range, Bottom

INLO

Floating Pt Value, E.U.

CWR Floating Pt

16

Output Range, Top

OUTHI

Floating Pt Value, Sig. Rng.

CWR Floating Pt

17

Output Range, Bottom

OUTLO

Floating Pt Value, Sig. Rng.

CWR Floating Pt

18

Output to use on restart

RESTART PREVIOUS (0), PRESET (1)

CWR Discrete

19

Output to use on failsafe

FSACT

HOLD (0), PRESET (1)

CWR Discrete

20

Restart preset value

PRESET

Floating Pt Value, E.U.

CWR Floating Pt

21

Track status

TRKSTAT NO TRACK (0), TRACK (1)

– WR Discrete

22

Track status data quality

TRKQ

GOOD (0), BAD (1)

– WR Discrete

23

Initial Scaled Result

RSC

Floating Pt Value, E.U. CWR

Floating

Pt

24

Maximum Output

MAXOUT

Floating Pt Value, E.U.

– – R Floating Pt

26

Input

INPUT

LSP or Floating Pt Value, E.U. CWR Floating Pt

40

Result

R

Floating Pt Value, Sig. Rng.

CWR Floating Pt

50

Result Quality

RQ

GOOD (0), BAD (1)

– WR Discrete

51

2-81