Built-in analog output block parameters – Micromod MOD: 30ML Functions Data Base Reference User Manual
Page 89
MOD 30ML Data Base Reference
BUILT-IN ANALOG OUTPUT BLOCK
2.8.2
Built-In Analog Output Block Parameters
The mnemonics, valid values, and data types for all fields that may be selected for
display and/or be used in making softwiring connections are listed in Table 2-11. A
description of each attribute is provided in the attribute list that follows the table.
Table 2-11. Built-In Analog Output Block Attributes, Valid Values, Mnemonics, and Data Types
Field Name / Attribute
Mnemonic
Valid Values
CWR Data Type
Attr
Version
VERSION
– – R Long State
00
Block Length
BLKLEN
– – R Count
01
State
STATE
RUN (0)
– – R Short State
02
Bad Inputs
BADINP
Rejected (0), Accepted (1)
CWR Discrete
03
Diagnostic Group
SUPPGRP NONE, 1 to 7
CWR Long State
04
I/O communications error
COMMERRS
ENABLE (0), SUPPRESS (1)
CWR Discrete
05
Unacked I/O comm. error
COMMERR
U
NO (0), YES (1)
– WR Discrete
06
Active I/O comm. error
COMMERRA
NO (0), YES (1)
– – R Discrete
07
OUTPUT Error
OUTERRS ENABLE (0), SUPPRESS (1)
CWR Discrete
08
Unacked Output error
OUTERRU NO (0), YES (1)
– WR Discrete
09
Active Output error
OUTERRA NO (0), YES (1)
– – R Discrete
10
Output Number
OUTNUM
1, 2
C – R Long State
11
Output Circuit Error
ERROR
– WR Short State
12
Mode
MODE
MANUAL (0), AUTO (1)
CWR Discrete
13
Action
ACTION
REVERSE (0), DIRECT (1)
CWR Discrete
14
Input Range, Top
INHI
Floating Pt Value, E.U. CWR
Floating
Pt
15
Input Range, Bottom
INLO
Floating Pt Value, E.U.
CWR Floating Pt
16
Output Range, Top
OUTHI
Floating Pt Value, Sig. Rng.
CWR Floating Pt
17
Output Range, Bottom
OUTLO
Floating Pt Value, Sig. Rng.
CWR Floating Pt
18
Output to use on restart
RESTART PREVIOUS (0), PRESET (1)
CWR Discrete
19
Output to use on failsafe
FSACT
HOLD (0), PRESET (1)
CWR Discrete
20
Restart preset value
PRESET
Floating Pt Value, E.U.
CWR Floating Pt
21
Track status
TRKSTAT NO TRACK (0), TRACK (1)
– WR Discrete
22
Track status data quality
TRKQ
GOOD (0), BAD (1)
– WR Discrete
23
Initial Scaled Result
RSC
Floating Pt Value, E.U. CWR
Floating
Pt
24
Maximum Output
MAXOUT
Floating Pt Value, E.U.
– – R Floating Pt
26
Input
INPUT
LSP or Floating Pt Value, E.U. CWR Floating Pt
40
Result
R
Floating Pt Value, Sig. Rng.
CWR Floating Pt
50
Result Quality
RQ
GOOD (0), BAD (1)
– WR Discrete
51
2-81