Micromod MOD: 30ML Functions Data Base Reference User Manual
Page 36
MOD 30ML Functions
DISPLAY INTERFACE BLOCK
05
Faceplate Comm Error (FPCOMS) .................................................................................. CWR
The error “FACEPLATE COMMUNICATIONS ERROR” (event code 4) is reported if an error
occurred when trying to communicate with the faceplate. Instances are counted in
CMERRCTR (attribute 30) or BFULLCTR (attribute 29).
ENABLED 0
Faceplate
communication error is enabled.
SUPPRESSED 1 Faceplate communication error is suppressed.
06
Faceplate Communication Error Unacknowledged
(FPCOMU)................................... – WR
If the faceplate communication error diagnostic is enabled, the unacknowledged status
indicates if the diagnostic is or is not acknowledged.
NO
0 Diagnostic error is acknowledged.
YES
1 Diagnostic error is unacknowledged (not writeable).
07
Faceplate Communication Error Active (FPCOMA) ...................................................... – – R
If the faceplate communication error diagnostic is enabled, the active status indicates if the
diagnostic is active even after acknowledgment.
NO
0 Diagnostic error is not active.
YES
1 Diagnostic error is active.
08
No Keyboard Response (NOKBDS) ................................................................................ CWR
The error “NO KEYBOARD RESPONSE”.(event code 5) is reported if the faceplate failed to
respond when keyboard data was requested. Instances are counted in KBERRCTR (attribute
31).
ENABLED
0 No Keyboard Response error is enabled.
SUPPRESSED 1 No Keyboard Response error is suppressed.
09
No Keyboard Response Unacknowledged
(NOKBDU) ................................................. – WR
If the no keyboard response error diagnostic is enabled, the unacknowledged status
indicates if the diagnostic is or is not acknowledged.
NO
0 Diagnostic error is acknowledged.
YES
1 Diagnostic error is unacknowledged (not writeable).
10
No Keyboard Response Active (NOKBDA) .................................................................... – – R
If the no keyboard response error diagnostic is enabled, the active status indicates if the
diagnostic is active even after acknowledgment.
NO
0 Diagnostic error is not active.
YES
1 Diagnostic error is active.
11 Reserved
12
Faceplate Version (FPVER) ............................................................................................ – – R
This is the software version of the faceplate presented as a number 0.0 to 25.5.
13
Device Tag (DEVTAG) ..................................................................................................... CWR
Up to 8 ascii characters identifying the instrument. Displayed on the second line of the top
level device display on the front panel of the instrument.
14
Power Up Display User Tag (PUPDISP) ........................................................................ CWR
2-28