PROCESS ALARM DISPLAY BLOCK

2.6.2

Process Alarm Display Block Parameters

The mnemonics, valid values, and data types for all fields that may be selected for display
and/or be used in making softwiring connections are listed in Table 2-7. A description of each
attribute is provided in the attribute list that follows the table.

Table 2-7. Process Alarm Display Block Attributes, Valid Values, Mnemonics, and Data Types

Field Name / Attribute

Mnemonic

Valid Values

CWR Data Type

Attr

Version

VERSION 1, 2

– – R Long State

00

Block Length

BLKLEN

– – R Count

01

State

STATE

RUN (0), HOLD (1), OFF (2),
DEBUG (3)

CWR Short State

02

Bad Inputs

BADINP REJECTED(0)

ACCEPTED(1),

CWR Discrete

03

Alarm Priority

PRIORITY 0 to 255 (0 = No

Unacknowledged Alarm)

CWR Long State

04

Alarm Activate Condition
(Trip Condition)

TRIPCOND LESS(0), LESS EQUAL(1),

GREATER (2), GREATER
EQUAL (3), EQUAL (4),
NOT EQUAL (5), or
DEVIATION (6)

CWR Short State

05

Suppress calculation?

SUPPRES
S

NO (0), YES (1)

CWR Discrete

06

Unacknowledged

U

FALSE (0), TRUE (1)

– WR Discrete

07

Unacknowledged Quality

UQ

GOOD (0), BAD (1)

– WR Discrete

08

Alarm Active

A

FALSE (0), TRUE (1)

– WR Discrete

09

Active Quality

AQ

GOOD (0), BAD (1)

– WR Discrete

10

Report events?

REPORT

NO (0), YES (1)

CWR Discrete

11

Alarm Activate Value
(Trip Point)

TRIPVAL

Local data for Floating-Point,
Count, Date, Msec Time,
Discrete, Short State, or
Long State data types.

CWR Same as

ALARMINP

12

Line 1 Text

TAG1

1-8 character ASCII string

CWR ASCII

13

Line 2 Text

TAG2

1-8 character ASCII string

CWR ASCII

14

Hi Range

HRNG

Top of alarm input range

CWR Same as

ALARMINP

15

Lo Range

LRNG

Bottom of alarm input range CWR Same as

ALARMINP

16

Alarm Input

ALARMINP LSP or local data

CWR Floating Pt,

Count, Date,
Msec Time,
Discrete,
Short State,
Long State,

17

Ack Input

ACKINP

NONE or LSP

C – R Discrete

18

Hysteresis

HYST

0.000000 to any positive
Floating Point Value

CWR Floating Pt

19