CONFIGURATION EXAMPLES

3.3.2

BASICPID (PID WITH DISPLAY) COMPOUND

The BASICPID compound is a fully functional single PID loop for the MOD 30ML controller
that includes the blocks and connections shown in Figure 3-2. The compound can be added
to an existing strategy which was saved previously or it can be used in a new strategy which
has been initiated as described in Section 3.3.

Features of the BASICPID compound are as follows:

• Built-in input and output connections are made to a single block representing the single loop

PID compound.

• MOD 30ML display connections, display script, control and alarm tune list and state table

(external file equivalent is STATE.TXT) are preconfigured.

• Additional features, such as more Process Alarm Display blocks, can easily be added.


3.3.3

PID Display Configuration Overview

The BASICPID compound consists of a PID block, a Display block, a Tune List block for
control and alarm parameters, and process connections that use built-in analog input and
outputs. This compound provides a basic working model of a PID loop. All ranges are set for
0 to 100 and a current type input and output is used.

Figure 3. 35. PID with Display Compound Blocks

3-29