Micromod MOD: 30ML Functions Data Base Reference User Manual
Page 37

MOD 30ML Functions
DISPLAY INTERFACE BLOCK
Choose a display to appear on the instrument front face at power up.
DEVICE
0
Power up display is the *DEVICE* display (top level display).
USER
Power up display is a user display from the Edit Display List. The
user field will be active to enter a display tag from the display list (the
display's position in Display List is stored as number).
PREVIOUS
65535 Power up display is the previous display.
15
Current Display (CURDISP) ............................................................................................. – – R
Display currently on the faceplate (stored as display number).
16
Current Access Level (CURACCS) ................................................................................. – – R
Current level of access.
OPERATE
0
Base operating level.
TUNE
1
Tune access enabled.
CONFIGURE 2
Configure access enabled.
17
Access Timeout (ACCTIME) ............................................................................................ C – –
The time in minutes (1 - 54) that the tune and configure access levels will timeout and return
to the operate level after last keyboard activity.
NONE
0
No timeout. Current access level will not timeout and change.
USER
1 to 54 Current access level will timeout and change 1 to 54 minutes after
last keyboard activity. Enter 1 to 54 in the subsequent field.
18
Min Low Alarm Priority (MINLOPRI) .............................................................................. C – R
All process alarms with priority >= this value (2 - 255) are considered LOW priority for display
purposes.
19
Diagnostics: Display Flash (FLSHDIAG) ....................................................................... CWR
Use to specify if an unacknowledged diagnostic will cause the entire display to flash. The
LED always flashes on an unacknowledged diagnostic.
NO
0
display flashing is disabled for an unacknowledged diagnostic.
YES
1
an unacknowledged diagnostic will cause the entire display to flash.
20
Diagnostics: Beep (BEEPDIAG)......................................................................................CWR
Use to specify if an unacknowledged diagnostic will cause the beeper to beep.
NO
0
beeping is disabled for an unacknowledged diagnostic.
YES
1
an unacknowledged diagnostic will cause the beeper to beep
21
Diagnostics: Flash/ Beep Rate (DFLSHRAT)................................................................. CWR
Diagnostic flash rate for LED, display and beeper.
SLOW
0
flash rate as set by slow off and on counts.
FAST
1
flash rate as set by fast off and on counts.
2-29