beautypg.com

Totalizer block connections, State table data, Display operation – Micromod MOD: 30ML Functions Data Base Reference User Manual

Page 131

background image

MOD 30ML Functions

CONFIGURATION EXAMPLES

Totalizer Block Connections

PID.PVI

------->

Totalizer.ANALINP (input for totalizing)

Totalizer.TC

----------> PIDDISP.I10

(permits display access to the run, hold,
stop and reset commands of the totalizer)

Totalizer.CMD ----------> TOTDISP.I4

(totalized value to be displayed)

Totalizer.TC

----------> TOTDISP.I1


State Table Data

ACTIOND, 8, "????????"
{
0, "NONE";
1, "RESET";
2, "STOP";
3, "RUN";
4, "HOLD";
}


Display Operation
Unless other changes were made in the strategy to cause a different behavior, the instrument
will come up in a manual mode with a local set-point. The output is displayed on the bottom
line. Pressing the scroll key once causes the set-point to be displayed on the bottom line.
Pressing the scroll key a second time causes the totalized value to be displayed on the
bottom line.

To enter the totalizer commands menu, press the TAG key at any time. This causes the
display to switch to the totalizer commands display. The totalized value will be on the second
line. The word “CMD” will appear next to the scroll key and the up and down arrows will be
illuminated. The lower display will state “NONE”. Pressing the up key causes “RESET” to
appear on the bottom line and “ENT” will flash next to the scroll key. Pressing the enter key
(scroll key) causes the reset operation to be enacted. If the enter key is not pressed the
action will time out, reset will not be enacted, and “NONE” will re-appear on the bottom line of
the totalizer commands menu.

This same operation applies to the STOP, RUN and HOLD commands. Each of these
commands are accessed after entering the totalizer commands display and pressing the up
key for each command.

Pressing the TAG key at any time causes the PID display to return.

3-37