Able, Nterpreting the, Tatic – MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 94: Witch transfer code, Loadbp)

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

78

#

Message

Explanation

29

OVLOAD

Load current is high

30

UPS-CM

One or more UPS’s not responding

31 STRTUP Startup

time-stamp

32 ------

N.A.

Each message is formatted as follows:

Time – HH:MM:SS

Date – YY:MM:DD

Data – DC voltage between + and – terminals for all events except LOADBP and STSW status for
LOADBP events. (See below.)

Even start (IN) and end (OUT)

Description – (See Table 12 above)

Event number – 0 through 255, 255 being the most recent

Example:

11:23:56 10.01.28 865 IN -> E.P.O. 254

This message means that at 11:23:56 on January 28

th

2010, Emergency Power Off alarm was

registered as event 254; dc voltage at the time was 865 V being a sum of (V+ -N) and (V- -N).

Table 13: Interpreting the Static Switch transfer code (LOADBP)

The STSW transfer code, given as a decimal, is the sum of the eight components listed in this table.
Each component has its own weight if detected, and a weight of zero if not detected.

C

OMPONENT

WEIGHT

C

ONDITION DESCRIPTION

1

Inverter voltage blackout for >3 ms.

2

Inverter peak voltage low (brownout) (<185 V for 3x400 V, <92.5 V for 3x208 V).

4

Inverter peak voltage high (>400 V for 3x400 V, >200 V for 3x208 V).

8

Frequency beyond limits (45-65 Hz).

16

Inverter average voltage low (<185 V for 3x400 V, <92.5 V for 3x208 V).

32

Inverter average voltage high (>260 V for 3x400 V, >130 V for 3x208 V)..

64

Load transfer command received from the controller (not manual).

128

Load transfer command received from the Static Switch (manual key press).

Example: If LOADBP data = 67 = (64+2+1), this means that three conditions were present:
 (64) Instruction to transfer the load was issued by the controller.
 (2) Low peak voltage detected.

(1) Voltage blackout encountered.