4 check ip communication with controller, Check ip communication with controller, Igure – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 69: Etwork, Onnections screen
![background image](/manuals/337597/69/background.png)
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
53
5.14.4 Check IP Communication with Controller
This test is designed to verify that the System Controller is properly configured for communication
and that the Web server built-in into the System Controller is functioning properly.
1.
Use an RJ45-to-RJ45 crossed cable to attach a laptop computer to the Ethernet (RJ45)
port on the rear panel of the System Controller.
2.
Configure the Network Connections of the laptop computer to make sure the computer
is in the same domain as the UPS. (Note: the details of the following configuration
procedure are for the Windows XP operating system. The configuration procedure will
differ for other operating systems.)
a.
Right click on the My Network Places icon on your desktop and select Properties.
Figure 59: Network Connections screen
b.
When the Network Connections screen appears, right-click on Local Area
Connection and select Properties.