8.12.3.5

Setting up the Dry Alarms

1. Select

Dry, Alarms:

[Main Menu > SETUP > (password) > Ent > Service > Configure]

1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND

Figure 235: Service > Configure menu

2. Select

DryN Association:

[Main Menu > SETUP > (password) > Ent > Service > Configure > DRY, Alarms]

1> dry1 association 4> dry4 association
2> dry2 association 5> dry5 association
3> dry3 association 6> dry6 association
7> enable / disable alarms

Figure 236: Dry relay menu

3.

Use arrow keys to set associations between dry contacts and alarms, and then press
Ent:

[Main Menu > SETUP > (password) > Ent > Service > Configure > DRY, Alarms > dry1
association]

Associate dry contact #01 with alarm/s
0 0 1 1 2 2 3 3 0=del
1...5....0....5....0....5....0.2 1=add
-------------------------------- alm#01

Figure 237: Set dry contact N alarm associations

4.

Use arrow keys to enable or disable alarms, and then press Ent:

[Main Menu > SETUP > (password) > Ent > Service > Configure > DRY, Alarms > enable /
disable alarms]

ENABLE OR DISABLE ALARMS/s
0 0 1 1 2 2 3 3 0- Dis
1...5....0....5....0....5....0.2 1-Ena
-------------------------------- ALM#01

Figure 238: Enable / disable alarms