2 total number of upss, 3 total number of batteries, Total number of upss – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 134: Total number of batteries, Igure, Ervice, Onfigure menu, Et total number of, Et total number of batteries
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
118
8.12.3.2
Total Number of UPSs
1. Select
# OF UPSs (total):
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 227: Service > Configure menu
2.
Use the arrow keys to set the total number of UPSs and then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (total)]
Set number of UPSs (total)
04 (02 redundant)
Figure 228: Set total number of UPSs
8.12.3.3
Total Number of Batteries
1. Select
# OF BATT:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 229: Service > Configure menu
2.
Use the arrow keys to set the total number of batteries and then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF BATT]
Set Number Of Batteries (0 to 3)
02
Figure 230: Set total number of batteries