beautypg.com

The power+ built-in web interface, 1 preliminaries to use of the web interface, Ower – MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 154: Built, Eb interface, Preliminaries to use of the web interface, Igure, Controller rear panel

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

138

9. T

HE

P

OWER

+

BUILT

-

IN

W

EB INTERFACE

The Power+ built-in Web interface enables you to monitor and control the Power+ from a
distance, using a PC over an Ethernet network. All that is required is an HTML browser such as
Microsoft’s Internet Explorer.

9.1

Preliminaries to use of the Web interface

To enable the Power+ Web interface:

1.

Consult with your Network Administrator to obtain an IP address for your Power+, and
the appropriate mask and gateway address.

2.

Configure the Power+ with the IP address. This is done from the Power+ main menu as
follows:

a.

Setup > (enter your password, then press Ent; default password is 8 left arrows)
> Service > SC2012 > Network.

b.

From the Network menu, choose IP Address and enter the assigned IP address.

c.

From the Network menu, choose Gateway and enter the assigned Gateway
address.

d.

From the Network menu, choose Mask and set the assigned subnet mask.

e.

From the Network menu, choose Store to save the information just entered.

3.

Connect the Power+ to the local Ethernet network using the Ethernet (RJ45) port on the
rear panel of the Power+ controller. This is the port labeled “TCP/IP Port” on the left
side of the controller rear panel in Figure 292 below.

Figure 292: Power+ controller rear panel

4.

On a computer terminal that has connectivity to the Power+ IP address, open a Web
browser and enter the Power+ IP address in the URL bar. For example, type
//154.102.2.130 and press Enter. You should see the Web interface main screen (see
Figure 293 below).