beautypg.com

5 “control” main menu option, Control” main menu option, Igure – MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 161: Ontrol, Main menu option screen, Able, Ommands available on the, Screen

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

145

9.3.5

“Control” main menu option

The “Control” main menu option enables the user to initiate any of a number of UPS processes.
The commands available are described in Table 18 below .

Figure 298: The "Control" main menu option screen

Table 18: Commands available on the “Control” screen

M

ENU OPTION

D

ESCRIPTION

Load on bypass

Transfers the load to the bypass voltage.

Load on inverter

Transfers the load to the inverter.

Start battery test

Initiates a battery test. Note: it is recommended that a battery test not be
initiated when the when the UPS is operating near 100 % capacity and at
the same time the battery is known to be not fully charged or not
connected or otherwise faulty.

Abort battery test

Stop a battery test immediately.

LED test

The UPS beeps briefly and all of the LEDs on the control panel light up, to
reveal any faulty LEDs.

Shutdown

Shuts down the Power+. Power will continue to be available to the loads
from the bypass voltage.

Startup

Starts up the Power+ when it is in an “OFF” condition.

Restart

When the Power+ is “ON”, this command initiates a shutdown of the
Power+ followed by a startup.