12 activating ‘auto’ test, 13 enabling/disabling options, Activating ‘auto’ test – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 124: Enabling/disabling options, Igure, Attery setup menu, Ctivated, Test
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
108
8.10.12 Activating ‘Auto’ Test
1. Select ‘AuTo’ Test:
[Main Menu > SETUP > (password) > Battery]
1> Test-Voltage 5> Battery test…
2> Test Alarm 6> Capacity 0020 AH)
3> Current-Limit.. 7> ‘AuTo’ Test
4> Temp Compensat. 8> Enable/Dis Options
Figure 201: Battery setup menu
2.
The test is performed. Press Ent when done.
[Main Menu > SETUP > (password) > Battery > ‘Auto’ Test]
Max/estim time left : 00:00:00 /--:--:--
Battery test in progress for: 00:00:00
Batt. volt: 400.0V Batt.current: 010
Last test: PASSED Days left: 027
Figure 202: Activated ‘Auto’ test
8.10.13 Enabling/Disabling Options
1. Select
Enable/Dis Options:
[Main Menu > SETUP > (password) > Battery]
1> Test-Voltage 5> Battery test…
2> Test Alarm 6> Capacity 0020 AH)
3> Current-Limit.. 7> ‘AuTo’ Test
4> Temp Compensat. 8> Enable/Dis Options
Figure 203: Battery setup menu