3.
Using the arrow keys, set the battery test top time, and then press Ent:
[Main Menu > SETUP > (password) > Battery > Battery test…> Set Auto Battery Test Top Time]
Set top time for battery test
(1 – 9) hours
Enter = accept 05 Esc = discard
Figure 197: Set battery test top time
8.10.11 Setting the N
th
Battery Capacity
1. Select
Capacity 0020AH):
[Main Menu > SETUP > (password) > Battery]
1> Test-Voltage 5> Battery test…
2> Test Alarm 6> Capacity 0020 AH)
3> Current-Limit.. 7> ‘AuTo’ Test
4> Temp Compensat. 8> Enable/Dis Options
Figure 198: Battery setup menu
2. Select
Set Capacity of Battery #1 and then press Ent:
[Main Menu > SETUP > (password) > Battery > Capacity 00020AH)]
1> Set capacity of battery #1 (020 Ah)
Figure 199: Select Set capacity of battery #1
3.
Using the arrow keys, set the battery capacity, press Ent, and then set the capacity for
the next battery, if any:
[Main Menu > SETUP > (password) > Battery > Capacity 00020AH) > Set Capacity of Battery
#1]
Battery #01 Capacity setup
10 -990
Capacity :020 Ah
Figure 200: Set battery capacity