beautypg.com

Technical specifications, Echnical specifications, Able – MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 181: Echnical specifications for the, Rm100

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

165

16. T

ECHNICAL SPECIFICATIONS

Table 25: Technical specifications for the RM100 3x208 Vac

POWER

+

TECHNICAL DATA

Topology

True On-line Battery, Double Conversion, VFI

Construction

Modular parallel hot-plugged modules

Operation Continuous
Input
Voltage

3 × 208 Vac + N (3 x 120 Vac, N = Neutral)

Voltage range

+15 % and -25 %

Current

28 A per module – no inrush current at startup

Frequency

47 Hz–63 Hz

Power walk-in

> 60 sec.

Power Factor

0.99

THDI 5

%

Output
Rated power for 3-3 configuration:

10 kVA / 8 kW to 100 kVA / 80 kW

Frequency tracking range

±2 Hz

Slew rate

1 Hz / sec.

Voltage

3 × 208 Vac + N (3 x 120 Vac, N = Neutral)

Static Regulation

±1 %

Regulation for unbalanced load

±1 % for 100% unbalanced load

Dynamic resp. to 100% load step

±2 %

Overload

110 % for 10 min., 125 % for 60 sec., 1000 % for 1 cycle

Waveform Sinusoidal
THD

Less than 2 % for linear load

Load CF

4:1

Ac-Ac efficiency (nominal)

Up to 94 % at full load

Dc-Ac efficiency (nominal)

Up to 97 % at full load

Batteries
Dc-Link Voltage

±160 to ±216 Vdc

Quantity (in optional external cabinet)

2 x 32 x 12 Vdc (40 Ah)

Type

Sealed, lead acid, rechargeable

General
Maximum power dissipation (Po=8 kW)

N*510 W (N*998 BTU), where N = # modules

Ambient temperature
operation (up to 80 kVA):
operation (90 and 100 kVA)
storage:


+14 to +104

°F (-10 to +40 °C)

+14 to +86

°F (-10 to +30 °C)

-4 to +140

°F (-20 to +60 °C)

Relative humidity

95 % max., non-condensing

Altitude

1500 m without derating

Enclosure IP20
Cooling system

Multi-Fan with speed control (forced)

Standards

EMC

IEC 62040-2, under EMC 2004/108/EC

Design

IEC 62040-3

Safety

IEC 62040-1, under LVD 2006/95/EC

Low magnetic field radiation

EMF as per ICNIRP

All specifications are subject to change without notice.