Igure, Round studs on inside of batt, Cabinet roof – MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 48: Round bus bar at base of, Rear, Able, Ey to, Above, Figure 29 below, and, Table 6

background image

Gamatronic Electronic Industries Ltd.

32

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

Figure 28: Ground studs on inside of batt. cabinet roof

Figure 29: Ground bus bar at base of UPS rear

Table 6: Key to Figure 28 and Figure 29 above

I

TEM

#

G

ROUND

NAME

I

NSTRUCTIONS

3

B

ATTERY

CABINET

GROUND

CONNECTION

Connect a cable to either of the ground studs (10 mm diam.) in the
roof of the battery cabinet Figure 28 and connect the other end of the
cable to the ground bus bar at the bottom rear of the UPS.
Use a cable of 3/0 AWG, and a tightening torque of 250 pound-
inches (28.2 N-m) on both ends of the cable.
Recommended cable shoe: mfr. Panduit, cat.no. S3/0-76R-5.

4

UPS

GROUND

BUS BAR

On the UPS's ground bus bar (located at the bottom rear of the UPS)
connect the ground cable from the battery cabinet to the ground bolt
(10 mm diam.) shown as item 4 in Figure 29. Open the ground bolt,
slip on the cable shoe, and reclose the ground bolt.
Recommended cable shoe: mfr. Panduit, cat.no. S3/0-76R-5.