beautypg.com

MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 182

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

166

D

IMENSIONS

Cabinet exterior
dimensions (U.S.)

H = 80 in. (42U), W = 24 in., D = 39.4 in.

Cabinet exterior
dimensions
(metric)

H = 2020 mm (42U), W = 600 mm, D = 1000 mm

UPS

CAPACITY

(

K

VA)

10

20

30

40

50

60

70

80

90

90

N+1

Weight

(lbs)

424 446 469 491 514 536 559 581 604 626

Weight

(kg)

192.2 202.4 212.6 222.8 233.0 243.2 253.4 263.6 273.7 284.0

Weights do not include batteries or battery cabinet.

Acoustic Noise

Noise (dBA)
with half load

48 52 53 54 55 55.8 56.4 57 57.5 58

Noise (dBA) with
full load

51 54 55 57 58 58.8 59.4 60 60.5 61

SYSTEM CONTROLLER – TECHNICAL DATA
Microcontroller core

16 bit

Display

4 × 40 characters LCD with backlight

Other indicators

8 LEDs, buzzer

Analog input channels

3 for battery current measurement
1 for temperature measurement

Voltage-free user input channels
(dry contacts)

8

Real Time Clock (RTC)

Yes (operates for 2 weeks without power)

Power meter

kVA, kW, PF

Volt-free outputs (dry contacts)

6 outputs, rated 50V/1A

RS232 user port

Yes, isolated

Optional communication

TCP/IP, GPRS/SMS wireless communications (optional)

Communications with system modules

Serial, isolated

Events log

255 events

System operation without controller

Unchanged

On-screen parameters

Load bar-graph
3-phase voltages
3-phase currents
Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature

Alarms
(floating output relay contacts,
each rated for max. 48 Vdc 1 A)

Ac failure
Dc failure
UPS module(s) failure
Load on bypass
Battery test failure
Over/under temperature
Overload

Power requirements

3 × 208 Vac / ±216 Vdc 15 W