MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 182
![background image](/manuals/337597/182/background.png)
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
166
D
IMENSIONS
Cabinet exterior
dimensions (U.S.)
H = 80 in. (42U), W = 24 in., D = 39.4 in.
Cabinet exterior
dimensions
(metric)
H = 2020 mm (42U), W = 600 mm, D = 1000 mm
UPS
CAPACITY
(
K
VA)
10
20
30
40
50
60
70
80
90
90
N+1
Weight
(lbs)
424 446 469 491 514 536 559 581 604 626
Weight
(kg)
192.2 202.4 212.6 222.8 233.0 243.2 253.4 263.6 273.7 284.0
Weights do not include batteries or battery cabinet.
Acoustic Noise
Noise (dBA)
with half load
48 52 53 54 55 55.8 56.4 57 57.5 58
Noise (dBA) with
full load
51 54 55 57 58 58.8 59.4 60 60.5 61
SYSTEM CONTROLLER – TECHNICAL DATA
Microcontroller core
16 bit
Display
4 × 40 characters LCD with backlight
Other indicators
8 LEDs, buzzer
Analog input channels
3 for battery current measurement
1 for temperature measurement
Voltage-free user input channels
(dry contacts)
8
Real Time Clock (RTC)
Yes (operates for 2 weeks without power)
Power meter
kVA, kW, PF
Volt-free outputs (dry contacts)
6 outputs, rated 50V/1A
RS232 user port
Yes, isolated
Optional communication
TCP/IP, GPRS/SMS wireless communications (optional)
Communications with system modules
Serial, isolated
Events log
255 events
System operation without controller
Unchanged
On-screen parameters
Load bar-graph
3-phase voltages
3-phase currents
Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature
Alarms
(floating output relay contacts,
each rated for max. 48 Vdc 1 A)
Ac failure
Dc failure
UPS module(s) failure
Load on bypass
Battery test failure
Over/under temperature
Overload
Power requirements
3 × 208 Vac / ±216 Vdc 15 W