Igure, Sc2012, Menu – MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 141: Etwork menu, Etting an, Address

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

125

3. Select

Factory settings:

[Main Menu > SETUP > (password) > Ent > Service > SC2012]

1> Restart controller 3> Network…
2> Factory settings 4> Reset MBX
Your selection: 1 5> --------------
Enter if you are sure (else press Esc.!)

Figure 255: SC2012 menu

Default settings are implemented, a confirmation screen appears briefly and then the
controller restarts.

4. Select

Network:

[Main Menu > SETUP > (password) > Ent > Service > SC2012]

1> Restart controller 3> Network…
2> Factory settings 4> Reset MBX
Your selection: 1 5> --------------
Enter if you are sure (else press Esc.!)

Figure 256: SC2012 menu

5. Select

Set IP ADDRESS:

[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]

1> Set IP ADDRESS 157.211.000.253
2> Set GATEWAY 157.211.000.251
3> Set MASK 255.255.255.000
4> Store 5> SNMP factor Select:1

Figure 257: Network menu

6.

Use the arrows keys to set an IP address and press Ent:

[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network > Set IP ADDRESS]

Set IP ADDRESS

157.211.000.252

Figure 258: Setting an IP address