beautypg.com

Igure, Rimp, Type cable shoes recommended for all ground cables – MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 47: Round studs on, Cabinet roof, View from below, Able, Ey to

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

31

Figure 27 through Figure 29 below, and Table 5 and Table 6, detail the ground connections for
the UPS and battery cabinet. It is recommended that all ground cables discussed here be
finished with cable shoes. For connections to the UPS and battery cabinets, the cable shoes
must have a bolt hole (item 1 in Figure 26) suitable for stud of 10 mm diameter and a cable
opening (item 2 in Figure 26) suitable for the cable sizes specified in Table 5 and
Table 6.

Figure 26: Crimp -type cable shoes recommended for all ground cables



Figure 27: Ground studs on UPS cabinet roof, view from below

Table 5: Key to Figure 27

I

TEM

#

G

ROUND NAME

I

NSTRUCTIONS

1

I

NPUT GROUND

CONNECTION

Insert the building ground cable through the roof or floor of the
UPS cabinet (Figure 20) and connect it to this stud (10 mm diam.).
Use a cable of 250 kcmil, and a tightening torque of
325 pound-inches (36.7 N-m).
Recommended cable shoe: mfr. Panduit, cat.no. S250-76R-5.

2

O

UTPUT

GROUND

CONNECTION

Connect a cable between this ground stud (10 mm diam.) and the
ground line on the electrical board. Use a cable of 250 kcmil,
and a tightening torque of 325 pound-inches (36.7 N-m).
Recommended cable shoe: mfr. Panduit, cat.no. S250-76R-5.