Gamatronic Electronic Industries Ltd.

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

57

6.

POWER+

ROUTINE START

-

UP

6.1

Start-up after Shutdown

This section describes the start-up procedures for the operator after a POWER+ shutdown.
After shutdown, the UPS on
, Alarm and Load indicators will flash.

After a normal POWER+ shutdown the display screen indicates a load of zero amps, the UPS
status is “OK, OFF”; the Static Switch status is “OK, BYP”.

LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW OK (BYP)

Figure 65: Main screen after a power shutdown

Figure 66: Main screen after a power shutdown indication

1.

Press twice on the On/Off button on the upper right of the system controller panel.

Wait about 2 minutes for the POWER+ to start up.

The following screen is displayed:

LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (ON)
L3:__________ 000A, 120V STSW OK (INV)

Status
indications

Figure 67: Main screen at power-up

Observe that UPS OK indication is now ON and the STSW OK now indicates INV.