2 setting battery floating voltage alarm, Setting battery floating voltage alarm, Igure – MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 102: C alarms menu, Et ac voltage hysteresis, Larm set menu, Attery floating charge alarm setup menu

background image

Gamatronic Electronic Industries Ltd.

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

86

4. Select

Set AC Alarms Hysteresis:

[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT]

1> SET AC HIGH & LOW ALARM LEVELS
2> SET AC ALARMS HYSTERESIS

PLEASE SELECT 1

Figure 127: Ac alarms menu

5.

Use the arrow keys to set value, press Ent, and then Esc:

[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT > Set AC Alarms
Hysteresis]

SET AC VOLT ALARMS HYSTERESIS VALUE
(1 – 20) VOLT

05

Figure 128: Set ac voltage hysteresis

8.8.2

Setting Battery Floating Voltage Alarm

1. Select

FLOAT VOLT:

[Main Menu > SETUP > (password) > ALARM SET]

1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------

Figure 129: Alarm set menu

2. Select

BATEND:

[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]

1> BATEND
2> BATLOW
3> ------
4> BAT-HI SELECT ITEM:1

Figure 130: Battery floating charge alarm setup menu