beautypg.com

2 dc wiring, Dc wiring – MaxPower Corp Gamatronic Power+ RM100 User Manual

Page 50

background image

Gamatronic Electronic Industries Ltd.

34

POWER+ RM100,

3

X

208

V, User Guide, Release 2.7ys

Ac input

Ac input bypass

50 kVA

Load

175 A

Ac input

Ac input bypass

60 kVA

Load

225 A

Ac input

Ac input bypass

70 kVA

Load

250 A

Ac input

Ac input bypass

80 kVA

Load

300 A

Ac input

Ac input bypass

90 kVA

Load

350 A

Ac input

Ac input bypass

100 kVA

Load

500 kcmils,

600 V,

75 °C copper wire

350 A

* The recommended wire size is based on a 100 kVA system. The required circuit breaker size is
based on the actual maximum power of the system in kVA.

5.4.2

Dc wiring

To connect the battery cabinet to the UPS, use wire size of 300 kcmils, rated for 600 V,
75 °C copper wire.