AINTENANCE BYPASS MODE

In maintenance bypass mode, the UPS output terminals continue to supply power to the load, but
the interior of the UPS is isolated from the main power flows. This enables a technician to work
safely on the UPS (after turning off the battery circuit breaker) without any interruption of power to
the load.

13.1

Putting the UPS in maintenance bypass mode

In normal operation, the UPS's ac circuit breakers are positioned as shown in Table 23.

Table 23: Normal operating position of the ac circuit breakers

R

ECTIFIER

AC INPUT

B

YPASS

AC INPUT

A

C OUTPUT

M

AINTENANCE

BYPASS

ON ON ON OFF

To put the system in maintenance bypass mode:

1.

Verify that the bypass indicator is lit on the Static Switch. (If it is not lit, the UPS cannot
go into bypass mode.)

2.

On the Controller front panel, press the INV/BYP button twice to put the UPS in bypass
mode.

3.

Verify that the bypass indicator is lit on the controller.

Then, operate the UPS's ac circuit breakers as follows:

4.

Switch ON the MAINTENANCE BYPASS circuit breaker.

5.

Switch OFF the AC OUTPUT circuit breaker.

6.

Switch OFF the RECTIFIER AC INPUT circuit breaker.

7.

Switch OFF the BYPASS AC INPTU circuit breaker.

The ac circuit breakers are now positioned as ac OUTPUT switch (the right-side switch).

8.

Switch OFF the rectifier INPUT switch (the left-side switch).

The switches are now positioned as shown in Table 24.

Table 24: Position of the ac CBs in maint. bypass mode

R

ECTIFIER

AC INPUT

B

YPASS

AC INPUT

A

C OUTPUT

M

AINTENANCE

BYPASS

OFF OFF OFF ON

9.

Switch OFF the BATTERY circuit breaker on the UPS rear panel.

The system is now in maintenance bypass mode.