4 setting battery integration alarm, Setting battery integration alarm, Igure – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 105: Nder temperature menu, Et battery minimum temperature alarm, Larm set menu
Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
89
4. Select
UNDER TEMPERATURE:
[Main Menu > SETUP > (password) > ALARM SET > Temperature]
1> OVER TEMPERATURE
2> UNDER TEMPERATURE
PLEASE SELECT
Figure 139: Over/Under temperature menu
5.
Use the arrow keys to set the battery minimum temperature alarm value, press Ent, and
then Esc:
[
Main Menu > SETUP > (password) > ALARM SET > Temperature > UNDER TEMPERATURE]
SET OVER TEMPERATURE ALARM VALUE
( 2 – 99) DEGREES
45
Figure 140: Set battery minimum temperature alarm
8.8.4
Setting Battery Integration Alarm
The Alarm Integration Factor determines the number of times that the controller polls and retries
to determine the UPS status before deciding on an error status. Setting the alarm integration
factor too low will cause spurious alarms to be generated; conversely, setting the alarm
integration factor too high may result in an alarm only being raised when it is already too late to
take corrective action.
1. Select
INTEGRAT.:
[Main Menu > SETUP > (password) > ALARM SET]
1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------
Figure 141: Alarm set menu