5 fuses, Fuses, Ac input fuses – MaxPower Corp Gamatronic Power+ RM100 User Manual
Page 51: Igure, C input fuses, Model

Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
35
5.5 Fuses
WARNING!
To reduce the risk of fire, replacement fuses must be of the same type and
rating as the original.
AVERTISSEMENT !
Pour réduire le risque du feu, les fusibles de rechange doivent être du mêmes
type et estimation que l'original.
AC INPUT FUSES
Verify that the appropriate ac fuses are present.
In the ac distribution module, the input for each UPS module is protected by a 32A fuse for each
phase, so that each module, including the controller, has 3 fuses (one each for the L1, L2, and L3
phases). Ten modules plus the controller would require 33 fuses, as illustrated in Figure 30. In
the 100 kVA model the fuse receptacles are numbered from right to left.
Figure 30: Ac input fuses (100 kVA model)